National Technical Regulation of Vietnam QCVN 06:2022/BXD on Fire safety of Buildings and Constructions

Dương Phạm

On November 30, 2022, the Minister of Construction of Vietnam promulgated Circular No. 06/2022/TT-BXD on the National Technical Regulation QCVN 06:2022/BXD on Fire safety of Buildings and Constructions.

According to the Circular, the arrangement of emergency exits for karaoke venues and discotheques shall satisfy the following requirements:

- Floors of karaoke venues and discotheques shall have no less than two emergency exits.

- Each floor may have one emergency exit when the following conditions are met:

+ Regarding buildings with a height for fire prevention and control of 15 m or lower, the area of each floor shall not be larger than 300 m2. Regarding buildings with a height for fire prevention control from 15 m to 21 m, the area of each floor shall not be larger than 200 m2.

+ The whole building is protected by an automatic fire suppression system.

+ The maximum number of people on each floor shall not exceed 20 people.

+ There must be at least one additional emergency exit from the floors leading to an open balcony or an open safe area on the rooftop, or stairs type 3

Note: An open area or open rooftop means it is exposed, and the covering part (if any) must ensure easy escape and rescue when the firefighting force approaches.

Circular No. 06/2022/TT-BXD comes into force as of January 16, 2023 and replaces Circular No. 02/2021/TT-BXD dated May 15, 2021.

>> CLICK HERE TO READ THIS ARTICLE IN VIETNAMESE

Above are the summary and notification of new documents for customers of THU VIEN PHAP LUAT. For more information, please send an email to [email protected].

5.678

More headlines

Most Viewed

Address: 17 Nguyen Gia Thieu street, Ward Vo Thi Sau, District 3, Ho Chi Minh City, Vietnam.
Phone: (+84)28 3930 3279 (06 lines)
Email: inf[email protected]

Copyright© 2019 by THƯ VIỆN PHÁP LUẬT
Editorial Director: Mr. Bui Tuong Vu

DMCA.com Protection Status